Inquiry #1: Please furnish Flow Charts for the sewer lines showing peak times and flow amounts. Please Identify high and low flows for a seven day period so we can design the bypasses accordinly.
Inquiry submitted 11/13/2013

Response #1:Refer to Addendum No. 2 dated Dec. 5, 2013 for the flow chart.
Response posted 11/14/2013




Inquiry #2: Reference Bid Item 205 - Structural Steel Bridge - Please indicate where the structural steel is located and what is to be paid as Structural Steel.
Inquiry submitted 11/13/2013

Response #1:Refer to Addendum No. 2 dated Dec. 5, 2013. Bid Item 205 has been deleted and Section 75-1.03A has been modified.
Response posted 11/14/2013




Inquiry #3: Reference Bid Item 252 - Miscellaneous Metal (Bridge) - Please indicate where this is located and what is to be paid as Misc. Metal (Bridge).
Inquiry submitted 11/13/2013

Response #1:Refer to Addendum No. 2 dated Dec. 5, 2013. Section 75-1.03A has been modified.


Response posted 11/14/2013




Inquiry #4: Sheet 647 of 985, Deck Details, shows a series of Sidewalk Access Opening (Manhole) in the Stage I Bridge sidewalk for access into the bridge. However, there are no Access Openings in the sidewalk of the Stage II Bridge for access into the bridge for the installation of the Deck Drainage and the future inspection of the Deck Drainage. Advise if access will be added.
Under which Bid Item will the Sidewalk Access Openings be paid?

Inquiry submitted 11/13/2013

Response #1:Refer to Addendum No. 2 dated December 5, 2013. Sheet 647 has been modified. Manhole frames and covers are paid as Miscellaneous Metal (bridge).


Response posted 11/14/2013




Inquiry #5: We request a bid postponement of at least 2 weeks due to numerous projects that will bid on the bid date.
Inquiry submitted 11/15/2013

Response #1:Bid has been postponed to January 9, 2014 by Addenda 1.
Response posted 11/18/2013




Inquiry #6: Page 46 of the Special Provisions states that the falsework openings for the Florence Ave OC are to be 49 feet wide in each direction. However, the the Stage Construction and Traffic Handling Plans indicate that the openings at the Florence Ave OC are 36 feet wide. Please advise which opening width is to be used.
Inquiry submitted 11/15/2013

Response #1:Refer to Addendum No. 2 dated Dec. 5, 2013. Section 12-4.02A has been modified.
Response posted 11/18/2013




Inquiry #7: Where can the requirements be found for the Class 4 Aggregate Subbase, bid item 148? Class 4 Subbase is not part of the Standards and I was unable to locate anything in the specials. Thank you for your help.
Inquiry submitted 11/18/2013

Response #1:Refer to plans issued under Addendum #3 dated December 20, 2013.
Response posted 11/18/2013




Inquiry #8: Your project #07-215954 states that it has a pumping station. Yet, there are absolutely no pump specs. Are there pumps on this project and if so, what kind of pumps do you need? Please advise.
Inquiry submitted 11/18/2013

Response #1:The information on pumping equipment is provided in Section 74, PUMPING EQUIPMENT AND CONTROLS, of the Standard Specifications.


Response posted 11/18/2013




Inquiry #9: Per Layout Sheet L-4, The MBGR on "FL2" line shows a 12B layout. No WB is shown on the quantity Sheet.
On the "A1" line it shows a AFTS with no WB attaching to the barrier. Also per Layout Sheet L-5 the "A1" line is showing a 16B layout but it's calling for MBGR to connect to barrier without a WB. Please clarify!

Inquiry submitted 11/19/2013

Response #1:Refer to Addendum #3 dated December 20, 2013.
Response posted 11/19/2013




Inquiry #10: I-5 @ Florence Ave. Contract No. 07-215954 – Pre-bid questions:

1) Sound Wall No. 103 Shts 714 – 753 of 985 we have observed Masonry Wall sections that appear to not have a Bid Item. The first section is from the beginning of the wall up station 47’-5 ¾” shown as “Retaining Wall (Masonry Block). The second section is called out as “Ret Wall Type 5 with spread footing (Mod) (Masonry Wall). Based on our takeoff, these sections of Masonry Wall are not included in Bid Item 196 “Masonry Block Wall” or Bid Item 225 “Sound Wall (Masonry Block)”. Please advise and/or clarify.

2) Summary of quantities (Q-2) indicates that there is 165 LF of Concrete Barrier (Type 736B Mod) on L-3 “FL3” line but L-3 does not indicate beginning or ending station, please provide.

3) Orr & Day Road Overhead (Shts 672-713 of 985) call out “Concrete Barrier (Type 60GA) and on Sht 673 of 985 the quantities section states 136 LF. There is no limits indicated on these structure plans and on Sht 690 of 985 it says “see Road Plans”. The Layout Plans 12-18 of 985 do not call out any “Concrete Barrier (Type 60GA)”. We have presumed that the limits of this barrier runs from the beginning of the Approach slab at Abutment 1 to the end of the Approach Slab at Abutment 2, is this correct?

4) Bid Item 287 is listed as Concrete Barrier (Type 60D) and quantified as 700 LF. We do not find this item listed in the Summary of Quantities sheets or shown on any of the Layout drawings. Please advise and/or clarify.

5) Bid Item 294 is listed as Concrete Barrier (Type 732A Modified) and quantified as 280 LF. We do not find this item shown on any of the structural drawings or quantified on any structure. Please advise and/or clarify.

6) Bid Item 296 is listed as Concrete Barrier (Type 736A) and quantified as 140 LF. We do not find this item shown on any of the structural drawings or quantified on any structure. Please advise and/or clarify.

Inquiry submitted 11/19/2013

Response #1:1. The information for bid item 166 RETAINING WALL (MASONRY WALL) is provided in Section “Bid Item List” of the contract special provisions.
2. Beginning and ending stations are shown on L-3 under item J and I on upper right corner.
3. Refer to Addendum No. 3 dated Dec. 20, 2013. Plan 672/985 has been modified.
4. Refer to Addendum #3 dated December 20, 2013. Concrete Barrier (Type 60D) will be deleted.
5. This item and work is shown on R-4 sheet page 440 of the contract Plans.
6. Refer to Addendum #3 dated December 20, 2013. This item of work is shown on R-1 sheet, page 437 of contract plans.
Response posted 11/19/2013




Inquiry #11: Do to the size and complexity of this and other projects that are bidding and with the holiday the week before, will you postpone the bid date at least two weeks?
Thank you,

Inquiry submitted 11/20/2013

Response #1:Yes, bid’s been postponed to January 9, 2014.


Response posted 11/20/2013




Inquiry #12: C-2 and C-3 show dotted lines that are not identified in the legend. Please clarify what to do with that pavement.
Inquiry submitted 11/20/2013

Response #1:The dotted lines shown on C-2 and C-3 are areas to crack existing concrete pavement as defined under lengend #4 (excluding the bridge deck). See addendum #2 for this item to clarify the legend and area.


Response posted 11/20/2013




Inquiry #13: Please confirm that RW 330 is getting built in Stage 1 Phase 3. It is not identified in the phasing cross-sections.
Inquiry submitted 11/20/2013

Response #1:Please see plans in Addendum #2, RW 330 is getting constructed under Stage 1-Phase 3B.


Response posted 11/20/2013




Inquiry #14: Given other projects bidding and holidays, please consider postponing the bid opening. We suggest a two week postponement. Thank you.
Inquiry submitted 11/20/2013

Response #1:Open date has been extended to January 9, 2014.
Response posted 11/20/2013




Inquiry #15: The notes on sheet 617 indicate that the existing Florence OC bridge "may require a shoring system after stage 1 bridge removal as determined by the Engineer." Please confirm that if required, this shoring will be paid for as extra work or please indicate the location(s) and temporary support loads that are required to shore this bridge.
Inquiry submitted 11/20/2013

Response #1:The information for payment for the shoring system at the existing bent cap overhang at Florence Avenue OC is provided in Section 15-4.01D of the contract special provisions.
Response posted 11/20/2013




Inquiry #16: This project bids the week after a major holiday. In addition, there is another large Caltrans project that is due within a week of this project. We respectfully request the bid date be extended a minimum of two weeks in order to complete our evaluation of the project requirements and prepare a competitive estimate.
Inquiry submitted 11/20/2013

Response #1:Open date has been extended to January 19, 2014.
Response posted 11/20/2013




Inquiry #17: Special Provisions, Section 2 states Bridge as built drawings are available. Please provide direction where these are available.
Inquiry submitted 11/21/2013

Response #1:For a project in District 7, 8, 9, 11 or 12, you must request them from the Office of Structure Maintenance and Investigations, fax (916) 227-8357, and are available at the Office of Structure Maintenance and Investigations, Los Angeles, CA, telephone (213) 897-0877.
Response posted 11/21/2013




Inquiry #18: Sound Wall No. 313 - Locations/Limits do not correspond to Sound Wall Structure plans. therefore, the pile data table is incorrect. Please revise.

Orr & Day Road OH - Abutment 1 Pile Layout (Sht 682/985), there is an error in the spacing for rows 3 & 4. It should be "13 @ 8'-7" = 111'-7"). This will also change the LF quantity for 24" CIDH Piles. Please revise.

Inquiry submitted 11/21/2013

Response #1:Refer to Addendum #2 dated December 5, 2013 and Addendum #3 dated December 20, 2013.
Response posted 11/21/2013




Inquiry #19: Reference to Plant List And Planting Specifications on sheet PL-1, what is the size or height of Palm trees? What does number 33 stand for?
Inquiry submitted 11/22/2013

Response #1:Refer to plans issued under Addendem #3 dated December 20, 2013. Height of the palm tree is 33 feet. The number 33 stand for height of trees.
Response posted 11/22/2013




Inquiry #20: Referring to the detail named IRRIGATION SLEEVE IN PAVEMENT on sheet LD-2, what is the bid line item for this detail? Is this detail applied to irrigation pipes under sidewalk or median paving?
Inquiry submitted 11/22/2013

Response #1:Refer to plans issued under Addendum #3 dated December 20, 2013. Irrigation Sleeve in Pavement Details on LD-2 has been deleted.
Response posted 11/22/2013




Inquiry #21: There is a 6" irrigation crossover (see sheet IP-4)on on-ramp to route 5 but it does not show on IRRIGATION CROSSOVERS table (see sheet LD-2). Please clarify.
Inquiry submitted 11/22/2013

Response #1:Refer to plans issued under Addendum #3 dated December 20, 2013. The irrigation crossovers table in sheet LD-2 has been revised.
Response posted 11/22/2013




Inquiry #22: Sheet IP-2 shows there is a 1" WM Reclaimed Water. Is the system (mainline, lateral line, valves, etc.) recycled? Please clarify.
Inquiry submitted 11/22/2013

Response #1:Yes, the system is recycled water. Refer to Addendum #3 dated December 20, 2013.
Response posted 11/22/2013




Inquiry #23: Inquiry numbers 5,11,14 all asked for a bid extension. When will Caltrans let us know if the bid is going to be extended or not? In addition when will we see answers to the other 15 bidder inquiries?
Inquiry submitted 11/22/2013

Response #1:Open date has been extended to January 9, 2014.
Response posted 11/22/2013




Inquiry #24: Summary of Quantities Sheet 434 of 985 (Q-2) indicates that there is 266 lf of Concrete Barrier (Type 60GE) on Sheet L-2 between NB "A1" Station 320+50.00 and 332+50.00. Review of Sheet L-2 does on show this quantity of barrier. We find Concrete Barrier (Type 60G) in two locations and Concrete Barrier (Type GE) between "A1" Station 321+79.78 and 323+06.73 which is only 126.95 LF. Please revise and/or clarify.
Inquiry submitted 11/25/2013

Response #1:Refer to plans issued under Addendum #3 dated December 20. 2013.
Response posted 11/25/2013




Inquiry #25: On the project plans sheet No. 791, (Sound Wall No. 313" on barrier on retaining wall Detail), the page gives details in regards to the masonry wall reinforcement table and wall section. The question I have is in regards to the compressive strength of the CMU to be used.

Per this table at the top of the page, the entire wall 33,800 SQFT. + is to be "ALL" HIGHSTRESS CMU. Is this correct or can the updated 2010 standard plate, RSP B-15, dated 10-19-12 be used in lieu of sheet No. 791.

Per the RSP-B15 plate, which is exact, word for word, including reinforcing, with the exception of modified section. It states that a maximum amount of 11'-4" of Regular Strength CMU maybe used and any additional amount in height will have to be HIGH STRESS. There quite a big difference from using ALL HIGHSTRESS vs. 2'-0" H.S. for the wall. Can this plate be used for Soundwall No. 313?


Inquiry submitted 11/26/2013

Response #1:Refer to Section 5-1.02, "Contract Components," of the Standard Specifications.
Response posted 11/27/2013




Inquiry #26: When can we expect answers to the 25 unanswered bidders inquiries? There is only four more working days until this project bids.
Inquiry submitted 11/27/2013

Response #1:Per Addendum No.1, issued today, November 27, 2013, bids for this work will be opened on Thursday, January 9, 2014, instead of the origianl date of Thursday, December 5, 2013.
Response posted 11/27/2013




Inquiry #27: In addition to Inquiry #25. Sound wall No. 314, with sheet number 846, also has the same criteria in regards to High stress CMU question. If it were per plan, for both walls, 313 & 314, all 58,330 SQFT of CMU would have to be highstress, unless the updated RSP-B15 plate can be used. Please clarify.
Inquiry submitted 11/27/2013

Response #1:Refer to Section 5-1.02, "Contract Components," of the Standard Specifications.


Response posted 11/27/2013




Inquiry #28: ITEM 293-CONCRETE BARRIER (TYPE 60R MODIFIED- WHERE CAN I FIND THE DETAILS FOR THIS BARRIER?
Inquiry submitted 12/02/2013

Response #1:Please see Addendum #2 for the Details for Concrete Barrier (Type 60R (mod)).
Response posted 12/02/2013




Inquiry #29: Ref Bridge Deck Drain Sys Item 253: The qty in the bid book appears to be only the weight for the deck drains. Bid book item 253 = 1740 lbs & 12 deck drains D-1 = 1620+- lbs. There are not any details for the pipe on the bridge plans. Bridge plans page 647 note (1) says to see the road plans. Plan page 127 - DS 57 says to see the structure plans. It appears the bridge deck drain pipe has been left out. The pipe will likely start out as 6" dia. but because of the length of the runs it will change to 8" or larger. Details are needed.
Inquiry submitted 12/03/2013

Response #1:Refer to Addendum No.2 dated December 5, 2013 and Addendum No.3 dated December 20, 2013. Plans 616/985, 617/985, 619/985, 639/985 and 647/985 have been modified.
Response posted 12/03/2013




Inquiry #30: Deck Details Sheet 647/985 shows deck drainage pipe appear to terminate at the centerline of abutments. Reference to "Road Plans" sends me to Drainage plans D-3, 6, & 7. Having examined these drainage plans, I could not find where that bridge drains tie into any drainage structure. I don't think the Standard detail at an abutment applies since the drawing shows the terminus at the centerline of the abutmensts. . . Please assist me in finding the information or provide the information.
Inquiry submitted 12/16/2013

Response #1:The information for deck drainage pipe is provided on Sheets 105/985 and 647/985 of the current contract plans.


Response posted 12/16/2013




Inquiry #31: Per Addendum No. 2 and sheet Nos. 699, 734, 781 & 834 the aesthetic details for the CMU sound walls were changed. The new details added a 10"x4"x16" cap to the top of the walls. The only problem is that also affects the "H" noted in the plans.

The CMU heights for the sound walls are 11'-4" and 13'-4", but by using a 4" high unit now, the modular height is now off by 4". The sound wall's "H" either needs to be increased or decreased by 4" to fit the rest of the wall to an 8" modular block standard.

Since Item No. 225 is final pay, the quantity / SQFT. also needs to be adjusted.

Inquiry submitted 12/17/2013

Response #1:See changes issued in Addendum #3.
Response posted 12/17/2013




Inquiry #32: Reference response to Inquiry #28, "Please see Addendum #2 for the Details for Concrete Barrier (Type 60R (mod))."

We have review the documents issued with Addemdum #2 and do not find any details for Concrete Barrier (Type 60R (mod), so again, please advise where we can find the details for this barrier. It would be of great assistance if you would provide the drawing number.

Inquiry submitted 12/18/2013

Response #1:Details for Concrete Barrier (Type 60R(Mod)) were posted under Addendum #3, issued December 20, 2013.
Response posted 12/18/2013


Response #2:Details for Concrete Barrier (Type 60R(Mod)) were posted under Addendum #3, issued December 20, 2013.
Response posted 01/02/2014




Inquiry #33: Several utilities are shown as to be relocated (designated with ***) during construction by others on Sheets U-10 through U-15. however, these do not appear on the table provided in 5-1.36D. In addition, these are shown as existing on Sheets U-1 through U-7. (For example, PP1062886E, PP1062887E, PP1062888E)

Should we assume utilities that are shown to be relocated but not listed on the 5-1.36D table would be relocated prior to construction start on 5/12/2014?


Inquiry submitted 12/23/2013

Response #1:Utility PP 1062886E, PP1062887E, and PP1062888E will be relocated prior to 5/12/14.


Response posted 12/23/2013




Inquiry #34: In Section 5-1.36D, in the "utilities not arranged table" second item, PP2317236E and PP941583E are listed. These poles do not seem to be on the same line but ultimately appear to be joining. Is PP809548E also included?

Inquiry submitted 12/23/2013

Response #1:Refer to Addendum #4 dated January 3, 2014.
Response posted 12/23/2013




Inquiry #35: Referencing Inquiry # 3 (12/16/13) and prompt reply (12/16/13), and the sheets you referred me to (105 and sheet 647 issued in Addendum 3 on 12/20/13), I have examined both referenced sheets as well as the drainage profiles for ALL adjacent Drain systems (46, 57,70, 75, 76 and 77) and cannot find any reference to any structure which shows the 8" dia deck drains being tied in nor can I find the invert or offset of the tie in at one of these drain systems which is the invert needed to indicate that the deck drain system extends past the centerline. Please either provide the information (station, offset, invert) needed to extend the 8" diameter pipe to a drainage structure.
Inquiry submitted 12/24/2013

Response #1:Bid per plans and Contract Documents.
Response posted 12/24/2013




Inquiry #36: Addendum 2 - 8-1.04C sets the start date for Stage 1 Phase 3B as March 2, 2015 or later.
Addendum 2 - 10-13.03B requires Stage 1 Phase 3A to be complete within 7 months from contract start.

Given the Department set the start of construction as May 12, 2014 in 8-1.04C (addendum 2), the specifications above seem to conflict.

Please clarify.




Inquiry submitted 12/27/2013

Response #1:There is no conflict. Please bid per contract document.
Response posted 12/27/2013




Inquiry #37: According to "Revised Foundation Report for Florence Avenue OC. Bridge No. 53-3065 (Replace)", Mr. Pibulporn Vijitakula points out in sections 8.2, 8.3, and 10 that vibration and noise should be studied prior to construction. A recommendation is also strongly encouraged to provide pre and post construction surveys of properties.

No Bid Item number is reflected for the contractor to include pricing for these services. Will an addendum be issued to list these items?

Inquiry submitted 12/27/2013

Response #1:Bid per plans and Contract Documents.
Response posted 12/30/2013




Inquiry #38: Per Sheet No. 433, Summary of Quantities Q-1 shows Treated Wood Waste for removed Double MBGR at 149,664 lbs. is this correct? Please verify.

Also, where's the treated wood waste for removed MBGR? Please clarify.

Thank you very much.

Inquiry submitted 12/30/2013

Response #1:Refer to Addendum #4 dated January 3, 2014.
Response posted 12/30/2013




Inquiry #39: No responses have been posted since 8 days ago, what's the plan?
Inquiry submitted 12/31/2013

Response #1:Responses have been provided.
Response posted 12/31/2013




Inquiry #40: Since the permanent pavement delineation includes areas for different contracts and are not shown in the stage construction plans, can we assume that those areas will be done at the end of stage 6 of this contract?
Inquiry submitted 01/03/2014

Response #1:Yes, you may assume that other area not shown in the staging plans will be completed by the last stage.
Response posted 01/03/2014




Inquiry #41: Please clarify how we are to connect control wires for the new valves for Controller ICC - D to the proposed new location. The controller is shown to be within the island where the NB SB Connector Rd to Route 605 fork splits. There is no new crossover shown to cross that section. Is there an existing crossover that is not shown?
Inquiry submitted 01/03/2014

Response #1:Existing irrigation crossovers not shown but are located on the connector roads to NB I-5 and NB I-605. Locations are diagonally to Parkmead Street across both connector roads.


Response posted 01/06/2014




Inquiry #42: The drip irrigation shown on IP-3 along Florence Ave. has a note showing 4 lateral lines @ 13.67"/OC and 2 lateral lines @ 11.3"/OC. Should this be in-line drip tubing at those spacing and not lateral lines?
Inquiry submitted 01/03/2014

Response #1:These notes should be for drip line spacing.
Response posted 01/06/2014




Inquiry #43: Reference CIDH Concrete Pile Sleeve Details (Typ) on Sheet 941 of 985, Culvert Protection Structure Plans. This detail calls for a 16" ID PVC bond breaker typ. at all locations. 16" ID is not a standard size. Please confirm that 18" SCH 40 PVC (16.809" ID) is acceptable. Furthermore, PVC pipe is 3x more expensive than HDPE pipe. Since the pipe is merely being used as a bond breaker, please confirm that 18" SCH 40 HDPE Pipe is an acceptable alternate.
Inquiry submitted 01/06/2014

Response #1:Please bid per the current contract documents.
Response posted 01/06/2014




Inquiry #44: What type of erosion control blanket is need in line item #18 Temporary Erosion Control Blanket?
Inquiry submitted 01/08/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #45: Seed mix for the hydroseed seed is incorrect. The seeding rate is way too high.
Inquiry submitted 01/08/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #46: Please confirm that where the plans note to install a "wireless data service system" is not including the GPS time source device. otherwise, please provide which bid items the GPS device is to be incorporated into.
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #47: Please refer to plan sheets 551 through 554 and 555. Please confirm the contractor is to rely on the quantities the are shown on the plans sheets in its development of the proposal. Otherwise, please provide clarification.
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #48: Please refer to plan sheet 548. Please confirm the joint trench detail (incorporating the type 1 and type 3 conduits in the same trench even though shown separately on the plans) shown for " outside shoulder" installation will apply for trenches in "new pavement" areas as shown on the same page. Otherwise, please provide any deviations that are to be considered.
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #49: Please refer to plan sheet 574. Please provide the size and type of conduit for note 'B'. Otherwise, should the contractor use best practice for the bid?
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #50: Please refer to section 77-3.01B(1) regarding the Econolite controllers. Please confirm that all costs, including tech support and other related supply costs, excluding shipping and taxes is considered as part of the listed price of $53,794.
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #51: Please refer to sections 86-2.051B(1) and 86-2.053A(1). Please confirm that communication conduit in bridges are to be fiberglass.
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #52: Please refer to plan sheet 574. Please provide the size and type of materials for notes 'D' and 'E'. No contact information was provided to verify. Should the contractor use best practice for the bid?
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #53: Please refer to SECTION 86-2.06D(2). Is there a plan detail of this work to properly incorporate the work for this materials? No standard plans sheet details match this work. Please confirm that this work is only where shown on the plans for non-traffic rated pull boxes.
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #54: Please refer to plan sheet 510. Please clarify the working hours for the work as shown in these locations and if the the loops runs have to split or all go to the shoulder. Please confirm the boxes to where the stub-outs are to be installed or located are within the 5-foot of the edge of shoulder and at the locations where the loops are to be cut.
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #55: Please refer to plan sheets 563 through 565. Please provide a foundation detail for this work. Would this be a non-reinforced 24" diameter and 5' depth foundation?
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014




Inquiry #56: Please refer to SECTION 6-2.03 of the special provisions. Please confirm that all 2070 controller assemblies will be furnished on the project plans.
Inquiry submitted 01/09/2014

Response #1:Bid per plans and contract documents.
Response posted 01/09/2014






The information provided in the responses to bidder inquiries is not a waiver of Section 2-1.03, “Examination of Plans, Specifications, Contract, and Site of Work,” of the Standard Specifications or any other provision of the contract, nor to excuse the contractor from full compliance with the contract. Bidders are cautioned that subsequent responses or contract addenda may change a previous response.