Contract 10-0A0594

The responses to bidder's inquiries, unless incorporated into a formal addendem to the contract, are not a part of the contract and are provided for the bidder's convenience only. In some instances, the question and answer may represent a summary of the matters discussed rather than a word-for-word recitation. The availability or use of information provided in the responses to bidder's inquiries is not to be construed in any way as a waiver of the provisions of Section 2-1.03 of the Standard Specifications or any other provision of the contract, the plans, Standard Specifications or Special Provisions, nor to excuse the contractor from full compliance with those contract requirements. Bidders are cautioned that subsequent responses or contract addenda may affect or vary a response previously given.

Q) Regarding the type III CF, sheet E1 note 1,everything for both meters is listed as metered, but there is no main disconnect listed for meter 2. Is meter 2 supposed to have a 100/2 circuit breaker as a main disconnect, similar to meter 1?

A) Each meter should have a separate 100 Amp 2-Pole main circuit breaker.